At Spares Universe,we provide safe, durable, and affordable NSN part fulfillment solutions for customers within a wide variety of industries. This includes our selection of dependable Sensor Opaque Parti items like NSN 6350-01-469-3167. If you are interested in purchasing part number 500-095112C by Cerberus Pyrotronics Inc, we encourage you to begin by submitting the Request for Quote (RFQ) form below to receive a competitive quote in 15 minutes or less. Using the details you provide in your form, including shipping deadlines, desired quantities, and more, we will find a solution for sourcing part number 500-095112C that caters to your particular situation.
Note : We Will Not Share Your Information To Any Third Parties.
Part number 500-095112C is produced by Cerberus Pyrotronics Inc under the CAGE Code 0A0E0, and this manufacturer is a trusted entity on our Approved Vendor List (AVL) who follows a strict level of quality assurance in their practices. They are also part of our vast supply network which allows for expedited shipping solutions for domestic and international customers alike. If you would like to explore other products with the NSN 6350-01-469-3167 or similar parts, we invite you to check out our page of 6350 Miscellaneous Alarm Signal And Security Detection Systems products or look at the list of related items below.
MRC | Criteria | Characteristic |
---|---|---|
FEAT | Special Features | PLUG-IN, 2 WIRE, MULTI-SENSOR DETECTOR, PHOTOELECTRIC (FOR SMOKE) AND THERMAL SENSING UNITS; COMPATIBLE WITH MXL FAMILY OF CONTROL PANELS; ELECTRICALLY COMPATIBLE WITH EXISTING MXL DETECTOR ACCESSORIES; REQUIRES P/N 500-095687, MODEL DB-11C (MOUNTING BASE, SERIES 11) FOR SOME OLDER MXL SYSTEMS; DUST RESISTANT; FIELD CLEANABLE PHOTO CHAMBER; SOLID STATE, NON-MECHANICAL THERMAL SENSOR; MICRO PROCESSOR BASED ELECTRONICS; MODEL FPI-32 PROGRAMMER/TESTER (NOT INCLUDED) USED TO ELECTRONICALLY PROGRAM AND VERIFY DETECTORS ADDRESS; FPI-32 ALLOWS USER TO CHANGE DEVICE FROM FP-11C TO OLDER DETECTOR ID WITHOUT HAVING TO REPROGRAM CONTROL PANEL; MULTI-COLOR LED FLASHES GREEN FOR NORMAL CONDITION, AMBER FOR DETECTOR FAULT, AND RED, WHEN INSTRUCTED BY PANEL, FOR ALARM CONDITION; CAPABLE OF BI-DIRECTIONAL COMMUNICATION WITH CONTROL PANEL; CURRENT REQUIRES 0.750 AMPS; PLUS 32 TO PLUS 100 DEG. F OPERATING TEMP; 0 TO 93 PERCENT HUMIDITY NON-CONDENSING; ULC LISTED |
MRC | Decoded Requirement | Clear Text Reply |
APGF | Design Type | NONTRIPOD MOUNTING |
FTLD | Functional Description | FIRE DETECTION UNIT, CHECKS FOR SMOKE AND THERMAL VARIATIONS, RELAYING DATA TO CONTROL PANEL |
ABMK | Overall Width | 2.300 INCHES NOMINAL |
AKWC | Electrical Power Source Relationship | OPERATING |
BRQN | Media Detected | SMOKE |
ADAV | Overall Diameter | 6.000 INCHES NOMINAL |
TMDN | Type/Model Designation | FP-11C |